TP-6735 7/17 45Section 4 Controller
4.8 Faults
Fault c odes and conditions are shown in the table on the
following pages, Figure 4-8. Fault conditions are
classified as warnings or shutdowns.
4.8.1 Warnings
The controller displays a fault code but the generator set
does not shut down on a warning. The controller resets
automatically after a warning condition is corrected.
4.8.2 Shutdowns
Under a fault shutdown condition, the generator set
shuts down automatically and the controller displays a
fault code. In some cases, the engine cooldown cycle
runs before the engine shuts down.
Shutdown switches (such as the low oil pressure switch
or high engine temperature switch) on the generator set
will automatically reset w hen the problem is corrected.
However, the fault condition at the controller does not
clear until the controller is reset.
The generator set cannot be restarted until the fault
condition is corrected and the controller is reset. See
Section 4.8.5 to reset the controller after a fault
shutdown.
4.8.3 ATS Communication Errors
An ATS fault can be caused by the following conditions.
D When a Model RRT transfer switch is used, an ATS
fault indicates that communication with the interface
board on the transfer switch has been lost. The
generator set shuts down. Check the connection to
the ATS interface board.
D If an RRT transfer switch is connected after the
controller has powered up, the ATS warning is
displayed. To clear the fault, disconnect and then
reconnect battery power to the controller.
4.8.4 Fault Code NoEC
The RDC and DC controllers display the fault code
NoEC (no engine configuration setting) when the
controller parameters have been lost or reset to the
default settings. Do not replace the controller
because of a NoEC fault. Change the Ec parameter to
the setting shown in Figure 4-12 for the generator set
model. Also check the Uu setting and change it, if
necessary. See Section 4.10 and Installation Manual
TP-6733.
The controller parameters may reset to the default
settings if the power to the controller is repeatedly
connected and disconnected (for example, when the
battery is connected or disconnected during installation
or service). To prevent controller reset when connecting
or disconnecting the battery, remove controller fuse F3
before disconnecting or reconnecting the battery
cables. See Section 4.3.1.
A service replacement controller also displays NoEC
and requires this procedure to set the parameters at
installation. See TT-1568, provided with the
replacement controller, for instructions.
Models 14/20RES: Use the RDC controller keypad or
Kohlerr SiteTecht software to s et the RDC controller
parameters. Follow the instructions in generator set
Installation Manual TP-6733 or see TP-6701, SiteTech
Software Operation Manual.
Models 14/20RESL: Use Kohlerr SiteTecht software
to set parameters on the DC controller. See TP-6701,
SiteTech Software Operation Manual, for instructions.

Table of Contents

Other manuals for Kohler 14RES

Question and Answer IconNeed help?

Do you have a question about the Kohler 14RES and is the answer not in the manual?

Kohler 14RES Specifications

General IconGeneral
BrandKohler
Model14RES
CategoryPortable Generator
LanguageEnglish

Summary

Safety Precautions and Instructions

Accidental Starting

Precautions to prevent unintended engine startup and associated hazards.

Battery Safety

Warnings and procedures for handling battery acid and gases.

Hazardous Gases

Hazards of carbon monoxide and fuel vapors, and mitigation procedures.

Mechanical and Electrical Hazards

Safety warnings for noise, voltage, and moving parts during operation and service.

Section 1 Specifications

Engine Specifications

Detailed technical specifications for the generator engine models.

Alternator Specifications

Technical specifications related to the generator's alternator.

Torque Specifications

Torque values for various fasteners used in the generator set.

Section 2 Scheduled Maintenance

Service Schedule

Intervals for performing maintenance tasks on the generator set.

Lubrication System

Procedures for checking and changing engine oil and filter.

Air Cleaner Service

Procedures for servicing the engine's air cleaner element.

Section 3 Troubleshooting

Initial Checks

Common problems to check before replacing parts.

Troubleshooting Chart

A reference table listing generator set faults, causes, and remedies.

Section 4 Controller

Controls and Indicators

Identification and explanation of controller user interfaces and indicators.

Faults

Explanation of fault codes, warnings, and shutdowns displayed by the controller.

Controller Configuration and Adjustment

Steps for configuring and adjusting controller settings and parameters.

Section 5 Component Testing and Adjustment

Voltage Adjustment

Procedures for adjusting generator output voltage and frequency.

Governor System

Testing and adjustment of the engine governor system for speed control.

Fault Shutdown Tests

Procedures to verify the operation of overspeed, overcrank, and LOP shutdowns.

Section 7 Wiring Diagrams

Schematic Diagram

Electrical schematic diagram for the generator set.

Related product manuals