EasyManuals Logo
Home>Kohler>Portable Generator>14RES

Kohler 14RES User Manual

Kohler 14RES
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
TP-6735 7/17 53Section 4 Controller
4.10.5 SiteTech Software
A personal computer running Kohlerr SiteTecht
software can be used to configure and adjust the RDC
and DC controllers. See TP-6701, SiteTech Software
Operation Manual, for PC connection and software
operation instructions.
See Figure 4-13 for the settings. Refer to TP-6701,
SiteTech Software Operation Manual, for instructions.
Appendix F contains a list of controller parameters that
can be viewed and adjusted using SiteTech. The
Access column in the table shows which parameters
can only be viewed (Read or Locked), and which
parameters can be changed using the software (Write).
SiteTech software is also used to update the firmware
on the RDC and DC controllers. See TP-6701 for
instructions.
SiteTech can be used to calibrate the voltage. See
Section 4.11.
4.11 Calibration
The controller can be calibrated for utility v oltage using
using a personal computer connected to the RDC/DC
controller. Kohlerr SiteTecht software is required for
calibration.
Note: Controller firmware version 2.04 or higher is
required for calibration. See Section 4.10.3 for
instructions to check the firmware version
number.
4.11.1 Calibrate Function
The RDC/DC controller can be calibrated using
SiteTech. Measure the actual utility voltage across L1
and L2, and enter the measured value into SiteTech as
described in the following procedure. See Figure 4-14.
SiteTech Group Parameter Value
Equivalent
RDC
Parameter
Setting
How to Enter
Genset System Configuration Genset System Voltage 240 Uu01 Type in
230 Uu06 Type in
Genset System Frequency 60 Uu01 Drop-down box
50 Uu06 Drop-down box
Genset Voltage Phase Connection Single Phase Uu01 or Uu06 Drop-down box
Genset Info Engine Model Number
CH--740*
(14RES or 14RESL)
Ec13
Type in*
Drop-down box
CH--1000*
(20RES or 20RESL)
Ec14
Type in*
Drop-down box
Genset Model Number 14RES
14RESL
20RES
20RESL
none Type in
Genset Serial Number See nameplate none Type in
Engine Serial number See nameplate none Type in
* With SiteTech v ersions prior to 2.3, type in CH--740 or CH--1000 with capital letters and dash exactly as shown.
Figure 4-13 Controller Setup Using SiteTech Software

Table of Contents

Other manuals for Kohler 14RES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 14RES and is the answer not in the manual?

Kohler 14RES Specifications

General IconGeneral
BrandKohler
Model14RES
CategoryPortable Generator
LanguageEnglish

Related product manuals