EasyManuals Logo
Home>Kohler>Controller>APM402

Kohler APM402 User Manual

Kohler APM402
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #75 background imageLoading...
Page #75 background image
TP-6694 9/20 75
2.7.12 Analog Inputs
Displays the selected programming user-defined analog notice, warning, and shutdown inputs. These inputs provide a multitude
of choices for configuring customized auxiliary inputs. See the figure titled: Analog and Digital Inputs for a list of analog input
choices. For descriptions of the inputs listed refer to the following sections:
System Fault Warning Lamp with Digital Displays
System Fault Shutdown Lamp with Digital Displays
Status and Notice Digital Displays
There is an optional 2 input/5 output (I/O) module board available that can provide two additional analog (or digital) inputs.
The displays for analog inputs appear as shown below and have an acceptable operating range (0-5 VDC). The analog input
selection typically requires entering four valueslow warning, high warning, low shutdown, and high shutdown.
AIn A1 (analog input A1) standard (reserved and not user programmable)
AIn A2 (analog input A2) standard (Identified as A1 on SiteTech™ software)
AIn B1 (analog input B1) with I/O module board
AIn B2 (analog input B2) with I/O module board
All analog input selection and setup adjustments are done using SiteTech™ software. The following terms and descriptions are
part of the setup procedure.
Enabled. This menu indicates whether or not the input is enabled. If the input is not enabled, the controller will ignore
this input signal.
Inhibit Time Delay. The inhibit time delay is the time period following crank disconnect during which the generator set
stabilizes and the controller does not detect the fault or status event. The controller will ignore the input until the inhibit
time expires. If the inhibit time is set to zero, the input is monitored at all times, even when the generator is not running.
The inhibit time delay range is from 0 to 60 seconds.
Time Delay (shutdown or warning). The time delay follows the inhibit time delay. The time delay is the time period
between when the controller first detects the fault or status event and the controller warning or shutdown lamp
illuminates. The delay prevents any nuisance alarms. The time delay range is from 0 to 60 seconds.
Analog Inputs
Analog - - >
Inputs
AIn A1
#####
AIn B1
#####
AIn B2
#####

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler APM402 and is the answer not in the manual?

Kohler APM402 Specifications

General IconGeneral
BrandKohler
ModelAPM402
CategoryController
LanguageEnglish

Related product manuals