6 Commissioning/Start-up/Shutdown
36 of 92
KSB Delta Macro
1983.843/04-EN
6.2.4.2 Fluid temperature
Table12: Temperature limits of the fluid handled
Permissible fluid temperature Value
Maximum +60°C
+25 °C to DIN 1988 (DVGW)
3)
Minimum 0°C
6.2.5 Minimum flow rate
Table13: Minimum flow rate per pump in manual mode
Size Minimum flow rate per pump
[l/h]
Movitec 2B 200
Movitec 4B 400
Movitec 6B 600
Movitec 10B 1100
Movitec 15C 1900
Movitec 25B 2800
Movitec 40B 4600
Movitec 60B 6100
Movitec 90B 8500
Movitec 125B 12500
6.3 Shutdown
6.3.1 Stopping
1. Set the master switch to 0.
2. Set the manual-0-automatic selector switch to 0.
3
Applies to the handling of drinking water (Germany and the Netherlands only)