10 Related Documents
KSB Delta Macro
69 of 92
1983.843/04-EN
Parameter Description Value range and dependencies Factory setting Access level Read Access level Write Re-start
required
2-2-1-2 Pump 2 Automatic Manual-Off Everybody Display/Customer -
Manual-Off
Manual-On
2-2-1-3 Pump 3 Automatic Manual-Off Everybody Display/Customer -
Manual-Off
Manual-On
2-2-1-4 Pump 4 Automatic Manual-Off Everybody Display/Customer -
Manual-Off
Manual-On
2-2-1-5 Pump 5 Automatic Manual-Off Everybody Display/Customer -
Manual-Off
Manual-On
2-2-1-6 Pump 6 Automatic Manual-Off Everybody Display/Customer -
Manual-Off
Manual-On
2-2-2 Rainwater operating mode - - Everybody Nobody -
2-2-2-1 Rainwater pump 1 Automatic Manual-Off Everybody Customer -
Manual-Off
Manual-On
2-2-2-2 Rainwater pump 2 Automatic Manual-Off Everybody Customer -
Manual-Off
Manual-On
10.2.2.3 Timers
Table31: Timers parameters
Parameter Description Value range and dependencies Factory setting Access level Read Access level Write Re-start
required
2-3 Timer - - Everybody Nobody -
2-3-1 Start delay time 0…99.9s 3s Everybody Service -
2-3-2 Stop delay time 0…99.9s 3s Everybody Service -
2-3-3 Minimum runtime 0 … 999s 180s Everybody Service -
2-3-4 Minimum runtime correction
step
0 … 99 s (calculated due to operating
mode)
10s Everybody Service -