KSB Delta Macro
73 of 92
1983.843/04-EN
Parameter Description Value range and dependencies Factory setting Access level Read Access level Write Re-start
required
2-5-1-2-1 Additional source Flow switch None Everybody Service -
2-5-1-2-2 Delay time for system stop 0 … 99s 10s Everybody Service -
2-5-1-2-3 Delay time reset 0 … 99s 2s Everybody Service -
2-5-1-3 Pressure sensor on suction side - - Everybody Nobody -
2-5-1-3-1 Minimum suction-side pressure
for system stop
0 … maximum pressure sensor range 1bar Everybody Service -
2-5-1-3-2 Minimum suction-side pressure
for reset
Minimum suction-side pressure for stop
… Maximum pressure sensor range
1.5 bar Everybody Service -
2-5-1-6 Flow switch - - - - -
2-5-1-6-2 Discharge pressure deviation 0 …10bar 1bar Everybody Service -
2-5-2 Leakage detection - - - - -
2-5-2-1 Leakage detection Disabled Disabled Everybody Service -
Enabled
2-5-2-2 Source Water detection integrated Water-detection
on-board
Everybody Service -
Leakage-detection by external device
2-5-2-4 Position Leakage of pump system Leakage of pump-
system
Everybody Service -
Overflow of tank
2-5-2-5 Response Message only Message only Everybody Service -
Message and stop all pumps
Message and close inlet valve
Message, close inlet valve and stop
pumps
2-5-2-6 Delay time leakage detection 0 … 99s 10s Everybody Service -
2-5-2-7 Delay time reset 0 … 99s 2s Everybody Service -
2-5-3 Hygienic functions - - - - -
2-5-3-1 General - - - - -
2-5-3-1-1 Hygienic functions Disabled Disabled Everybody Service -
Enabled
2-5-3-2 Temperature monitoring - - - - -
2-5-3-2-1 Temperature monitoring Disabled Disabled Everybody Service -
Enabled
2-5-3-2-2 Maximum temperature 0 … 70°C 25°C Everybody Service -
2-5-3-2-3 Minimum temperature 0 … 70°C 5°C Everybody Service -