61
7 Correcting Faults
7.3 Repair
WARNING!
Safety-relevant components!
Risk of malfunction if repaired improperly.
Only have repairs done by the manufacturer.
Do not attempt to make repairs yourself.
7.4 Information About the Repair Service
Please contact LAMTEC Service/Support if you have any questions.
Fault Causes Fault rectification
The flame monitor switches to fault
condition during operation.
The ignition flame has been extinguished.
Possible cause
- Pressure in combustion
chamber fluctuating.
Provide for differential pressure control on the
gas and air side.
- Gas and air pressures
fluctuating.
- Main flame is influenced
by flows in the combus
tion chamber or due to
external deflection.
Correct the installation position and power of
the ignition burner.
- No combustion air in the
combustion chamber.
Despite the closed gas valve, the
flame monitor outputs a flame
signal.
The gas valve is leaky, so
that a small flame arises.
Replace leaky gas valve.
LAMTEC GmbH & Co.KG
Sensors and Systems for Combustion
Technology
Wiesenstraße 6
D-69190 Walldorf
Hotline: +49 (0) 6227 / 6052-33
email: support@lamtec.de