9
CLIMATIC 50, user manual – Chillers ranges CL50-CHILLERS/IOM
/
0906-E
9
SCHEDULING
Function
Controlling operation of the unit according to the time and day
Description
CLIMATIC
TM
50 can handle 4 time zones over the 7 days of the week:
Zone unoccupied
Zone A
Zone B
Zone C
Starting time (hours and minutes) of each of these zones for each days of the week, can be set using menus
3211 to 3214, (press PROG key to change day).
3211 ! Starting time Unoccupied Zone (hour, minute)
3212 ! Starting time Zone A (hour, minute)
3213 ! Starting time Zone B (hour, minute)
3214 ! Starting time Zone C (hour, minute)
8h00 12h00 14h00 20h00
Monday
Unoccupied
ZA ZB ZC
Unoccupied
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
For each time zone the following set points can be adjusted:
1. Pump control type. Set point 3112, (refer to the “pump control” pages for more details).
2. Change Over rules for heat pump units. Set point 3311 must be set for each time zone
3. Heating and cooling temperature set points. Set point 3321 to 3325 for cooling and 3331 to 3335 for
heating (refer to the control set point pages for more details)
4. Compressor operation. Set point 3411 (refer to the compressor operation pages for more detailed
information)
With DS50, for each set point, press PROG key to change time zone and validate the right set point in the
right zone
Note: “Monday” is the first day of the week for the scheduling on CLIMATIC
TM
50
As a factory setting, only Zone A is activated 24hours a day, 7 days a week

Other manuals for Lennox CLIMATIC 50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC 50 and is the answer not in the manual?

Lennox CLIMATIC 50 Specifications

General IconGeneral
BrandLennox
ModelCLIMATIC 50
CategoryChiller
LanguageEnglish

Related product manuals