FAULT CODES
PUMP(S) CIRCUIT BREAKER(S) OPEN
Fault Code: 041, 042
Description
The thermal magnetic trip circuit breaker protecting the pump k has tripped
Action
Case 1 :
The unit only handles ONE pump
$ Immediate shut down of pump k.
$ Immediate shut down of the unit.
$ Fault signal shown on the display.
$ The remote fault signal is delayed by 6 minutes
Case 2
: The unit handles TWO pumps.
$ Immediate shut down of pump k.
$ Start up of the 2
nd
pump (refer to “EVAPORATOR PUMP(S) CONTROL” section for more details)
$ Fault signal 041 is shown on the display for Pump 1 and 042 for Pump 2
$ The remote fault signal is delayed by 6 minutes
Reset
The fault is automatically reset as soon as the pump circuit breaker is closed.
If the unit was stopped (case 1), the unit will restart automatically 20 seconds after the fault signal has
disappeared and the climatic 50 has restarted the pump.
Possible causes Solving the problem
Wrong wiring or tightening of the connections. Control all connections
Wrong setting on the circuit breaker
Set circuit breaker according with compressor
normal running current

Other manuals for Lennox CLIMATIC 50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC 50 and is the answer not in the manual?

Lennox CLIMATIC 50 Specifications

General IconGeneral
BrandLennox
ModelCLIMATIC 50
CategoryChiller
LanguageEnglish

Related product manuals