EasyManuals Logo
Home>Lennox>Chiller>CLIMATIC 50

Lennox CLIMATIC 50 User Manual

Lennox CLIMATIC 50
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
30
CLIMATIC 50, user manual – Chillers ranges CL50-CHILLERS/IOM
/
0906-E
30
FAULT CODES
INSUFFICIENT WATER FLOW RATE
Fault Code: 001
Description
The flow switch FSE is detecting a low water flow rate in the evaporator heat exchanger for more than 3
seconds
Action
$ Immediate shutdown of the whole unit.
$ A fault signal is shown on the display.
$ The remote fault signal is delayed by 6 minutes
Reset
The unit restarts automatically, 20 seconds after the flow switch detects a flow rate.
Possible causes Solving the problem
Problem with the pump control wiring. Check the pump connections
Problem with the flow switch wiring Check the flow switch connections
Dirty or clogged water filter. Clean the water filter.
Wrong setting of the flow switch. Check the flow switch settings.

Other manuals for Lennox CLIMATIC 50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC 50 and is the answer not in the manual?

Lennox CLIMATIC 50 Specifications

General IconGeneral
BrandLennox
ModelCLIMATIC 50
CategoryChiller
LanguageEnglish

Related product manuals