EasyManuals Logo
Home>Lennox>Chiller>CLIMATIC 50

Lennox CLIMATIC 50 User Manual

Lennox CLIMATIC 50
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
10
CLIMATIC 50, user manual – Chillers ranges CL50-CHILLERS/IOM
/
0906-E
10
ANTICIPATION – Heat pump mode only
Function
This allows an anticipated start-up in the morning depending on the outdoor temperature.
Description
This function only works for zone A, and allow the machine to move from unoccupied zone to zone A earlier if
the outdoor temperature is under a certain value.
This will allow the unit to anticipate a cool day.
This can be adjusted with set point 3221 and 3222.
3221 ! bottom of the slope (°C), Anticipation starting point .
3222 ! Slope in Minutes of anticipation per degrees
Example:
WA chiller with Zone A
starting at 8.00 am
3221 set at 3°C
3222 set at 10mn/°C
If outside temperature is
0°C, the zone A will start
at 7.30 am
Outside air
temp
Zone A starting
time
0°C
3°C
7.30 am
8.00 am

Other manuals for Lennox CLIMATIC 50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC 50 and is the answer not in the manual?

Lennox CLIMATIC 50 Specifications

General IconGeneral
BrandLennox
ModelCLIMATIC 50
CategoryChiller
LanguageEnglish

Related product manuals