84
CLIMATIC 50, user manual – Chillers ranges CL50-CHILLERS/IOM
/
0906-E
84
2BH 43
R L
[On/Off] Compressor, Heat pump, Circuit 2
2437
2CH 44
R L
not used
2DH 45
R L
not used
2EH 46
R L
not used
2FH 47
R L
not used
30H 48
R L
not used
31H 49
R L
not used
32H 50
R L
not used
33H 51
R L
[Dry contact] Digital Input, Free 3, BE50-J4-ID1 2181
34H 52
R L
[Dry contact] Digital Input, Free 4, BE50-J4-ID2 2182
35H 53
R L
[Dry contact] Digital Input, Free 5, BE50-J4-ID3 2183
36H 54
R L
[Dry contact] Digital Input, Free 6, BE50-J4-ID4 2184
37H 55
R L
[On/Off] Fan 1, High speed, Circuit 1 2614
38H 56
R L
[On/Off] Fan 2, Circuit 1 2615
39H 57
R L
[On/Off] Fan 3, Circuit 1 2616
3AH 58
R L
[On/Off] Fan 4, Circuit 1 2617
3BH 59
R L
[On/Off] Fan 5, Circuit 1 2618
3CH 60
R L
[On/Off] Fan 1, High speed, Circuit 2 2624
3DH 61
R L
[On/Off] Fan 2, Circuit 2 2625
3EH 62
R L
[On/Off] Fan 3, Circuit 2 2626
3FH 63
R L
[On/Off] Fan 4, Circuit 2 2627
40H 64
R L
[On/Off] Fan 5, Circuit 2 2628
LonWorks
Type Name NV Type NV Direction Index
WA LC DS50
ANL 1 I_Sp_WCool_1_BMS 105 input 1
ANL 1 O_Sp_WCool_1_BMS 105 output 1
[Occupation][Water SP] Required
maximum water temperature in °C.
Cooling set point
3321
(BMS)
ANL 2 I_Sp_WHeat_1_BMS 105 input 2
ANL 2 O_Sp_WHeat_1_BMS 105 output 2
[Occupation][Water SP] Required
minimum water temperature in °C.
Heating set point
3331
BMS
ANL 3 I_Sp_WCool_1_Uno 105 input 3
ANL 3 O_Sp_WCool_1_Uno 105 output 3
[Inoccupation][Water SP] Required
maximum water temperature in °C.
Cooling set point
3321
(Uno)
ANL 4 I_Sp_WHeat_1_Uno 105 input 4
ANL 4 O_Sp_WHeat_1_Uno 105 output 4
[Inoccupation][Water SP] Required
minimum water temperature in °C.
Heating set point
3331
Uno
ANL 17 O_Ia_TEEG 105 output 17
[Temperature] Intlet, Water
2112
ANL 18 O_T_Outside 105 output 18
[Temperature] Outdoor, Air
2111
ANL 19 O_Ia_TSEG 105 output 19
[Temperature] Outlet, Water
2113
ANL 20 O_Ia_P_HP_1 105 output 20
[Pressure] High, Circuit 1 (Bar)
2125
ANL 21 O_Ia_P_BP_1 105 output 21
[Pressure] Low, Circuit 1 (Bar)
2126
ANL 22 O_Ia_P_HP_2 105 output 22
[Pressure] High, Circuit 2 (Bar)
2135
ANL 23 O_Ia_P_BP_2 105 output 23
[Pressure] Low, Circuit 2 (Bar)
2136
ANL 24 O_Ia_P_HP_3 105 output 24
[Pressure] High, Circuit 3 (Bar)
2145
ANL 25 O_Ia_P_BP_3 105 output 25
[Pressure] Low, Circuit 3 (Bar)
2146
ANL 26 O_Ia_P_HP_4 105 output 26
[Pressure] High, Circuit 4 (Bar)
2155
ANL 27 O_Ia_P_BP_4 105 output 27
[Pressure] Low, Circuit 4 (Bar)
2156

Other manuals for Lennox CLIMATIC 50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC 50 and is the answer not in the manual?

Lennox CLIMATIC 50 Specifications

General IconGeneral
BrandLennox
ModelCLIMATIC 50
CategoryChiller
LanguageEnglish

Related product manuals