IOM – FLEXY II – 1007 – E Page 96
Chec k HP / LP safety switches
Install manifold gauges on t he circuit to be chec ked. Shut
do wn the a xial fans a nd wait for the HP s witch to s hut
do wn the co mpress or : 2 9b ar (+1 / -0) aut o-reset 22bar (+
- 0.7) Rec onnect fans. Switch off the centrifugal supply fan
and wait f or th e L P s witch to c ut out : 0. 5b ar (+ - 0.5) res et
1.5 bar ( +-0.5).
[] 15
Chec k outdoor fans and fan guards
Chec k the fan blades conditions and all fan guards and
protecti ons
o 5
Chec k position of all sensors
Chec k the good positioning and operation of all sensors of
all sens ors. Chec k th e val ues g i ven in t he c on trol s yste m.
Replace sensor if necessary
o 5
Chec k and clean if necessar y all fres h
air g rilles
Chec k the fr esh air grilles (if fitted). If dirt y or damage d,
remove them from unit and clean with high pr essure water
cleaner. Refit on unit onc e clean and dry.
o 5
Clean condensate drai n, indoor and
out door c oils (follo wing local
regulations)
Visuall y ch ec k t he c oils for dirt. If not to o dir t y, cleaning
wi th a l ig ht br ush ma y be e no ug h ( WAR N IN G: F i ns a nd
copper tubes are very fragile! Any damage WILL reduce
the perf ormances of the u nit). If ver y dirt y, deep i ndus trial
cleaning is required using de-greasing agents.(External
contractors must be c alled).
o / []
1h if
cleaning
Chec k el ectric heater element for
exc essi ve c orrosion
Isolate the unit; Pull t he electric heater o ut of t he heater
mo dul e bo x an d c hec k t he r esi sta nces of tr aces of
corrosion; R eplac e resistance as required;
o
1h if
replacement
Chec k anti-vi br at i o n mou nt i ng s , for
we ar an d t ear .
Visuall y ch ec k a nti-vi br at i o n mou nt i ng s on c om pr es s or s
and cen trifug al fa n. Replac e if da mag ed .
o
1h if
replacement
Chec k refrigeration circuit for traces of
acid in the oil
Take a sa mple of oil from the refrigeration circuit. []
Chec k Gl ycol concentration in the H WC
circuit
Chec k the glyc ol concentration in the pr essurised water
circuit. ( a concentrati on of 30% gives a protec tion down to
apro x. - 15°C) ch ec k t he circuit pressur e
[] 30
Chec k defrost cycle with 4-way val ve
inversion.
Switc h the unit t o heat p ump mo de. Ch ange t he s et poin t
to obtai n t he st andard defrost mo de and reduc e th e c ycle
time to t he min value. Chec k t he operatio n of t he defr ost
cycle.
[] 30
Gas burner module chec k for c orrosion
Pull out t he burn er to access th e t ubes (refer t o G as burner
section in the IOM)
[] 30
Sweepi ng an d cleaning t he gas burn er
Clean the i n-shot burners and the bl ower wheel lightly wit h
a br us h. S weep th e fl ue an d flue box. Wipe-off the d ust
from t he housing of the motor. Clean c ombusti on air inlet
louvers Pull-out baf fles fr o m the tu bes , s weep t he tu bes
CHECK FLUE BOX GASKET
[] 30
Gas su ppl y pressures / connectio ns
chec ks
refer to Gas burner secti on i n the IOM for det ails [] 15
Gas regulati on valve s ettings refer to Gas burner secti on i n the IOM for details [] 30
Chec k gas burner safety s witches refer to Gas burner secti on i n the IOM for details [] 30