IOM FLEXY II 1007 E Page 96
Chec k HP / LP safety switches
Install manifold gauges on t he circuit to be chec ked. Shut
do wn the a xial fans a nd wait for the HP s witch to s hut
do wn the co mpress or : 2 9b ar (+1 / -0) aut o-reset 22bar (+
- 0.7) Rec onnect fans. Switch off the centrifugal supply fan
and wait f or th e L P s witch to c ut out : 0. 5b ar (+ - 0.5) res et
1.5 bar ( +-0.5).
[] 15
Chec k outdoor fans and fan guards
Chec k the fan blades conditions and all fan guards and
protecti ons
o 5
Chec k position of all sensors
Chec k the good positioning and operation of all sensors of
all sens ors. Chec k th e val ues g i ven in t he c on trol s yste m.
Replace sensor if necessary
o 5
Chec k and clean if necessar y all fres h
air g rilles
Chec k the fr esh air grilles (if fitted). If dirt y or damage d,
remove them from unit and clean with high pr essure water
cleaner. Refit on unit onc e clean and dry.
o 5
Clean condensate drai n, indoor and
out door c oils (follo wing local
regulations)
Visuall y ch ec k t he c oils for dirt. If not to o dir t y, cleaning
wi th a l ig ht br ush ma y be e no ug h ( WAR N IN G: F i ns a nd
copper tubes are very fragile! Any damage WILL reduce
the perf ormances of the u nit). If ver y dirt y, deep i ndus trial
cleaning is required using de-greasing agents.(External
contractors must be c alled).
o / []
1h if
cleaning
Chec k el ectric heater element for
exc essi ve c orrosion
Isolate the unit; Pull t he electric heater o ut of t he heater
mo dul e bo x an d c hec k t he r esi sta nces of tr aces of
corrosion; R eplac e resistance as required;
o
1h if
replacement
Chec k anti-vi br at i o n mou nt i ng s , for
we ar an d t ear .
Visuall y ch ec k a nti-vi br at i o n mou nt i ng s on c om pr es s or s
and cen trifug al fa n. Replac e if da mag ed .
o
1h if
replacement
Chec k refrigeration circuit for traces of
acid in the oil
Take a sa mple of oil from the refrigeration circuit. []
Chec k Gl ycol concentration in the H WC
circuit
Chec k the glyc ol concentration in the pr essurised water
circuit. ( a concentrati on of 30% gives a protec tion down to
apro x. - 15°C) ch ec k t he circuit pressur e
[] 30
Chec k defrost cycle with 4-way val ve
inversion.
Switc h the unit t o heat p ump mo de. Ch ange t he s et poin t
to obtai n t he st andard defrost mo de and reduc e th e c ycle
time to t he min value. Chec k t he operatio n of t he defr ost
cycle.
[] 30
Gas burner module chec k for c orrosion
Pull out t he burn er to access th e t ubes (refer t o G as burner
section in the IOM)
[] 30
Sweepi ng an d cleaning t he gas burn er
Clean the i n-shot burners and the bl ower wheel lightly wit h
a br us h. S weep th e fl ue an d flue box. Wipe-off the d ust
from t he housing of the motor. Clean c ombusti on air inlet
louvers Pull-out baf fles fr o m the tu bes , s weep t he tu bes
CHECK FLUE BOX GASKET
[] 30
Gas su ppl y pressures / connectio ns
chec ks
refer to Gas burner secti on i n the IOM for det ails [] 15
Gas regulati on valve s ettings refer to Gas burner secti on i n the IOM for details [] 30
Chec k gas burner safety s witches refer to Gas burner secti on i n the IOM for details [] 30
MAINTENANCE PLAN

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox FLEXY II Series and is the answer not in the manual?

Lennox FLEXY II Series Specifications

General IconGeneral
BrandLennox
ModelFLEXY II Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals