Zoning CFM Tables
IMPORTANT
All recommended CFM settings are mid-range temperature rise values per stage per unit. All CFM combinations must be <79% indoor blower power.
Table 11. SLP98 Zoning
MODEL SLP98UH070
SLP98UH
090-36
SLP98UH
090-48
SLP98UH
090-60
SLP98UH110 SLP98UH135 SLP98DF070 SLP98DF090
SLP98DF
090-48/60
SLP98DF110
Absolute Min
CFM per zone
315 @ 64.7° 430 @ 64.6° 430 @ 64.6° 450 @ 61.7° 545 @ 64.6° 645 @ 64.6° 315 @ 64.7° 430 @ 64.6° 430 @ 64.6° 545 @ 64.6°
Recommended
Min CFM Per
Zone
350 @ 58.2° 440 @ 63.1° 485 @ 57.3° 485 @ 57.3° 620 @ 56.8° 705 @ 59.1° 350 @ 57.8° 445 @ 62.4° 485 @ 57.3° 615 @ 57.2°
Recommended
Max Air Flow
1025 @ 57.8° 1250 @ 63.0° 1375 @ 57.2° 1400 @ 57.5° 1725 @ 56.9° 2000 @ 59.3° 1025 @ 57.8° 1250 @ 62.2° 1375 @ 57.2° 1725 @ 57.4°
Table 12. SLP99 Zoning
MODEL SLP99UH070
SLP99UH
090-36
SLP99UH
090-48
SLP99UH
090-60
SLP99UH110 SLP99UH135 SLP99DF070 SLP99DF090
SLP99DF
090-48/60
SLP99DF110
Absolute Min
CFM per zone
315 @ 64.7° 430 @ 64.6° 430 @ 64.6° 505 @ 55.0° 545 @ 64.6° 645 @ 64.6° 315 @ 64.7° 430 @ 64.6° 430 @ 64.6° 545 @ 64.6°
Recommended
Min CFM Per
Zone
350 @ 58.2° 440 @ 63.1° 485 @ 57.3° 525 @ 52.9° 620 @ 56.8° 705 @ 59.1° 350 @ 57.8° 445 @ 62.4° 485 @ 57.3° 615 @ 57.2°
Recommended
Max Air Flow
1025 @ 57.8° 1250 @ 63.0° 1375 @ 57.2° 1525 @ 52.8° 1725 @ 56.9° 2000 @ 59.3° 1025 @ 57.8° 1250 @ 62.2° 1375 @ 57.2° 1725 @ 57.4°
Table 13. G71MPP Zoning
MODEL G71MPP-36B-070 G71MPP-36C-090 G71MPP-60C-090 G71MPP-60C-110 G71MPP-60D-135
Absolute Min CFM Per Zone 335 @ 69.1° 450 @ 70.0° 450 @ 70.0° 560 @ 69.4° 680 @ 69.4°
High Heating Airow Range 25 CFM inc 800 / 1100 1075 / 1250 1075 / 1500 1375 / 1900 1650 / 2050
Recommended Min CFM Per Zone 385 @ 60.1° 485 @ 64.9° 525 @ 60.0° 650 @ 59.8° 755 @ 62.5°
Recommended Max Air Flow 925 @ 60.1° 1150 @ 65.2° 1250 @ 60.0° 1600 @ 59.6° 1825 @ 62.4°