3
Zone Damper Transformer
The zone dampers are powered by a eld−provided 24VAC transformer.
Zone dampers typically require 6 to 12VA each depending on zone damper
manufacturer being used. The zone damper transformer must have an adequate
VA rating to serve all components (see recommendations in following table).
The damper control module (nominal 24VAC, 2AMP with 4 dampers closed)
and three in- zone thermostats require a total of 6VA to operate.
Table 1. Zone Damper Transformer Selection Chart
Catalog
Number
Size Description VA LOAD =
10P17 40VA
120 / 208 240VAC,
24VAC
Damper VA x number of dampers
+ 6VA (damper control module +
3 in -zone thermostats) = damper
transformer VA requirement.
10P87 50VA
12P61 75VA
Recommended Items Sold Separately
Lennox recommends for furnace applications the use of air bafes to help in
mixing the supply air for better Discharge Air Temperature Sensor accuracy.
Table 2. Recommended Air Bafes for Furnaces
Furnace Width Type Cat # Width
B 13X59 16”
C 13X60 19-1/2”
D 13X62 23”
Table 3. Electrical Box
Description Catalog Number
Electrical Box (4-in. Square)
83P74
Dimensions
9-1/4” (235mm)
6” (152mm)
2” (50mm)
Figure 1. Dimension