Test Run
Pre-Checks
Only perform test run after you have completed the
following steps:
Electrical Safety Checks Conrm that the unit’s
electrical system is safe and operating properly.
Refrigerant Leak Checks Check all are nut connec-
tions and conrm that the system is not leaking.
Conrm that suction and liquid valves are fully open.
Procedure
You should perform the Test Run for at least 30 minutes.
1. Connect power to the unit.
2. Press the ON/OFF button on the remote controller to
turn it on.
3. Let each function run for 5 minutes, and perform the
following checks:
Table 9. Test Run Checklist
Checks Pass Fail
No electrical leakage
Unit is properly grounded
All electrical terminals properly
covered
Indoor and outdoor units are solidly
installed
All pipe connection points do not leak
Water drains properly from drain hose
All piping is properly insulated
Unit performs COOL function properly
Indoor unit louvers rotate properly
Indoor unit responds to wireless
remote
Double-Check Line Set Connections
During operation, the pressure of the refrigerant circuit
will increase. This may reveal leaks that were not present
during your initial leak check. Take time during the Test
Run to double-check refrigerant line set connections and
verify there are no leaks.
1. Using the wireless remote control, return unit to the
normal operating temperature.
2. Using insulation tape, wrap the indoor refrigerant pipe
connections that you left uncovered during the indoor
unit installation process.
Ambient Temperature is Below 60ºF (16ºC)
After installation, conrm that all electrical wiring is
installed in accordance with local and national regulations,
and according to the installation instruction.
You cannot use the wireless remote control to turn on the
COOL function when the ambient temperature is below
60°F (16°C). In this instance, you can use the MANUAL
CONTROL button on the indoor unit to test the COOL
function.
1. Lift the front panel of the indoor unit, and raise it until
it clicks in place.
2. The MANUAL CONTROL button is located on the
right-hand side of the unit. Press it two times to select
the COOL function. See “Figure 29. Manual Control
Button”.
3. Perform Test Run as normal.
Terminal Block
Cover
Indoor Unit Control Box
Area (under front panel)
Manual Control Button
Figure 29. Manual Control Button

Other manuals for Lennox MCB Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MCB Series and is the answer not in the manual?

Lennox MCB Series Specifications

General IconGeneral
BrandLennox
ModelMCB Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals