Technical Data
2 Technical Data
2.1 Standards and Application Conditions
Conformity
CE Low Voltage (2006/95/EC) & EMC (2004/108/EC) Directives
Approvals
UL508C Underwriters Laboratories -Power Conversion Equipment
Input voltage phase imbalance
< 2%
Supported Power Systems
TT
TN
For central grounded systems, operation is permitted
without restrictions.
For corner grounded 400/500V systems, operation is
possible but reinforced insulation to control circuits is
compromised.
Humidity
< 95% non-condensing
Temperature range
Transport -25 … +70°C
Storage -20 … +70°C
Operation -10 … +55°C (with 2.5%/°C current derating above +40°C)
Installation height
0 - 4000m a.m.s.l. (with 5%/1000 m current derating above 1000m a.m.s.l.)
Vibration resistance
acceleration resistant up to 1.0g
Earth leakage current
> 3.5 mA to PE
Max Permissable Cable Length
(1)
<= 4.0 Hp (3.0 kW) 30 meters shielded, 60 meters un-shielded
=> 5.0 Hp (3.7 kW) 50 meters shielded, 100 meters un-shielded.
Enclosure
IP31/NEMA 1 IP65/NEMA 4X
NEMA 1 and NEMA 4X model enclosures are plenun rated in accordance with UL
508C and are suitable for installation in a compartment handling conditioned air.
Protection measures against
short circuit, earth fault, phase loss, over voltage, under voltage,
motor stalling, over temperature, motor overload
Compliance with EN 61000-3-2
Requirements
(2)
< 0.5kW with mains choke
0.5 ... 1kW with active filter
> 1kW without additional measures
Compliance with EN 61000-3-12
Requirements
(2)
16 ... 75amp Additional measures required for compliance with EN 61000-3-12
Operation in public supply networks (Limitation of harmonic currents i.a.w. EN 61000-3-2, Electromagnetic Compatibility
(EMC) Limits). Limits for harmonic current emissions (equipment input current up to 16A/phase).
(1) The stated cable lengths are permissible at default carrier frequencies (refer to parameter P166).
(2) The additional measures described only ensure that the controller meets the requirements of the EN 61000-3-2.
The machine/system manufacturer is responsible for the machine’s compliance with the regulations.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com

Other manuals for Lenze SMVector

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze SMVector and is the answer not in the manual?

Lenze SMVector Specifications

General IconGeneral
BrandLenze
ModelSMVector
CategoryInverter
LanguageEnglish

Related product manuals