Function
3.1 Pressure protection control
3.1.1 Pressure control on cooling mode
High pressure control
Low pressure control
Frequency holding : frequency (or RPM) is not increasing ( can decrease )
3. Protection control
Pressure range, kPa(psi) Compressor Fan Hot gas
Hot gas
Stop Stop
-
-
-
-5Hz/4sec. +100RPM/4sec.
Frequency holding Normal control
Normal control
-
Pressure range, kPa(psi) Compressor Fan
Stop Stop
ON
-5Hz/4sec -100RPM/4sec.
Normal control Frequency holding
Normal control
OFF
.
Ph 4003 (580.6)
P
h > 3448 (500.1)
P
h 3219 (466.9)
P
h < 3219 (466.9)
P
l 190 (27.6) after 1min.
Pl 190 (27.6) before 1min.
Pl 229 (33.2)
Pl 399 (49.2)
P
h : high pressure
P
l : low pressure