- 18 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Function
Note : Heating operation is not functional at an outdoor air temperature of 27 °C or more.
Cooling operation is not functional at an outdoor air temperature of 2 °C or less with indoor unit
combination of 10% or less
1.2 Compressor control
Fuzzy control : Maintain evaporating temperature(Te) to be constant on cooling mode and condensing
temperature(Tc) on heating mode by Fuzzy control to ensure the stable system performance.
[TC:47~51 °C(116.6~123.8 °F), Te:2~5 °C(35.6~41 °F)]
(1) Cooling mode
Te can be set various step at installation mode.
(2) Heating mode
Tc can be set various step at installation mode.
Note: By setting dip switch, Te and Tc are decided simultaneously.
1.1 Normal operation
1. Basic control
Min. pulse
Min. pulse
Min. pulse
Min. frequency