- 24 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Function
3.1.2 Pressure control on heating mode
n High pressure control
n Low pressure control
3.1 Pressure protection control
3.1.1 Pressure control on cooling mode
n High pressure control
n Low pressure control
h Frequency holding : frequency (or RPM) is not increasing ( can decrease )
h Frequency holding : frequency (or RPM) is not increasing (can decrease).
3. Protection control
Pressure Range Compressor Fan
Pd ≥ 4000 kPa(580.2 psi) Stop Stop
Pd > 3775 kPa(547.5 psi) -15 Hz / 10 seconds +100 RPM / 10 seconds
Pd ≥ 3650 kPa(529.4 psi) Frequency holding RPM holding
Pd ≥ 3480 kPa(504.7 psi) +2 Hz or less / 10 seconds RPM holding
Pd < 3480 kPa(504.7 psi) Normal control
Pressure Range Compressor Fan
Ps ≤ 110 kPa(15.9 psi) Stop (1 min. later) Stop
Ps ≤ 150 kPa (21.8 psi) -10 Hz / 10 seconds -100 RPM / 10 seconds
Ps > 150 kPa (21.8 psi) Frequency holding RPM holding
Ps > 185 kPa (26.8 psi) +2 Hz or less / 20 seconds -100 RPM / 10 seconds
Ps > 220 kPa (31.9 psi) +2 Hz or less / 10 seconds -100 RPM / 10 seconds
Ps > 260 kPa (37.7 psi) Normal control
Pressure Range Compressor Fan
Ps ≤ 50 kPa (7.3 psi) Stop (1 min. later) Stop
Ps ≤ 70 kPa (10.2 psi) -10 Hz / 10 seconds +100 RPM / 10 seconds
Ps ≤ 70 kPa (10.2 psi) Frequency holding RPM holding
Ps > 100 kPa (14.5 psi) +2 Hz or less / 20 seconds +100 RPM / 10 seconds
Ps > 185 kPa (26.8 psi) +2 Hz or less / 10 seconds +100 RPM / 10 seconds
Ps > 220 kPa (31.9 psi) Normal control
Pressure Range Compressor Fan
Pd ≥ 4000 kPa(580.2 psi) Stop Stop
Pd > 3415 kPa(495.3 psi) -15 Hz / 10 seconds -50 RPM / 10 seconds