Function
4.3 Night Low Noise Function
In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night
which has low cooling load.
Night low noise function setting method
CAUTION
• Request installer to set the function during installation.
• In case the function is not used, set the dip S/W OFF and reset the power.
• If ODU Hz and RPM change, cooling capacity may go down.
RPM / Time Settings
Service PCB DIP switch on : No.5
Select the mode using ’, ‘’ Button : “Func” Push
the ’ button
Select the Function using ’, ‘’ Button : “Fn3”
Push the ’ button
Select the Option using ’, ‘’ Button : “op1~op15”
Push the ’ button
Start the Night low noise function :
Save the selected option value in EEPROM
Step Judgment Time(Hr) Operation Time(Hr)
op1 8 9
op2 6.5 10.5
op3 5 12
op4 8 9
op5 6.5 10.5
op6 5 12
op7 8 9
op8 6.5 10.5
op9 5 12
op10
Continuous operation op11
op12
op13 6.5 10.5
op14 6.5 10.5
op15 6.5 10.5

Table of Contents

Other manuals for LG Multi V

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG Multi V and is the answer not in the manual?

LG Multi V Specifications

General IconGeneral
BrandLG
ModelMulti V
CategoryAir Conditioner
LanguageEnglish

Related product manuals