- 38 -
Copyright © 2020 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Specifications
Specifications
1. HR Unit
Model
PRHR022
PRHR022A
PRHR032
PRHR032A
PRHR042
PRHR042A
Max. Connectable No. of Indoor Units 16 24 32
Max. Connectable No. of Indoor Units of a branch 8 8 8
Nominal Input
Cooling 26 40 40
Heating 26 40 40
Net. Weight
kg 18 20 22
lbs 39.7 44.1 48.5
Dimensions
(WxHxD)
mm 801 x 218 x 617 801 x 218 x 617 801 x 218 x 617
Inch 31.5 x 8.6 x 24.3 31.5 x 8.6 x 24.3 31.5 x 8.6 x 24.3
Casing Galvanized steel plate
Connecting
Pipes
Indoor
Liquid Pipe [mm/inch] Ø 9.52[3/8]
Gas Pipe [mm/inch] Ø 15.88[5/8]
Outdoor
Liquid [mm/inch] Ø 9.52[3/8] Ø 12.7[1/2] Ø 15.88[5/8]
Low Pressure [mm/inch] Ø 22.2[7/8] Ø 28.58[1 1/8] Ø 28.58[1 1/8]
High Pressure [mm/inch] Ø 19.05[3/4] Ø 22.2[7/8] Ø 22.2[7/8]
Sound Absorbing Insulation Material Polyethylene Foam
Current
Minimum circuit Amps(MCA) 0.2
Maximum fuse Amps(MFA) 15
Power Supply
1 Ø, 220-240 V, 50 Hz / 1 Ø, 220 V, 60 Hz
1 Ø, 208/230 V, 60 Hz
Model
PRHR023
PRHR023A
PRHR033
PRHR033A
PRHR043
PRHR043A
Max. Connectable No. of Indoor Units 16 24 32
Max. Connectable No. of Indoor Units of a branch 8 8 8
Net. Weight
kg 14.9 16.7 18.2
lbs 32.8 36.8 40.1
Dimensions
(WxHxD)
mm 786 X 218 X 657 786 X 218 X 657 786 X 218 X 657
Inch 30.9 X 8.6 X 25.9 30.9 X 8.6 X 25.9 30.9 X 8.6 X 25.9
Casing Galvanized steel plate
Connecting
Pipes
Indoor
Liquid Pipe [mm/inch] Ø 9.52[3/8] – Ø 6.35[1/4]
Gas Pipe [mm/inch] Ø 15.88[5/8] – Ø 12.7[1/2]
Outdoor
Liquid [mm/inch] Ø 9.52[3/8] Ø 12.7[1/2] Ø 15.88[5/8]
Low Pressure [mm/inch] Ø 22.2[7/8] Ø 28.58[1 1/8] Ø 28.58[1 1/8]
High Pressure [mm/inch] Ø 19.05[3/4] Ø 22.2[7/8] Ø 22.2[7/8]
Sound Absorbing Insulation Material Polyethylene Foam
Power Supply
1 Ø, 220-240 V, 50 Hz / 1 Ø, 220 V, 60 Hz
1 Ø, 208/230 V, 60 Hz
2 Series
3 Series