Specifications
Model
PRHR063
PRHR063A
PRHR083
PRHR083A
Max. Connectable No. of Indoor Units 48 64
Max. Connectable No. of Indoor Units of a branch 8 8
Net. Weight
kg 27.2 30.7
lbs 60 67.7
Dimensions
(WxHxD)
mm 1 113 X 218 X 657 1 113 X 218 X 657
Inch 43.8 X 8.6 X 25.9 43.8 X 8.6 X 25.9
Casing Galvanized steel plate
Connecting
Pipes
Indoor
Liquid Pipe [mm/inch] Ø 9.52[3/8] – Ø 6.35[1/4]
Gas Pipe [mm/inch] Ø 15.88[5/8] – Ø 12.7[1/2]
Outdoor
Liquid [mm/inch] Ø 15.88[5/8]
Low Pressure [mm/inch] Ø 28.58[1 1/8]
High Pressure [mm/inch] Ø 22.2[7/8]
Sound Absorbing Insulation Material Polyethylene Foam
Power Supply
1 Ø, 220-240 V, 50 Hz / 1 Ø, 220 V, 60 Hz
1 Ø, 208/230 V, 60 Hz
Notes:
1. Voltage range : Units are suitable for sue on electrical systems where voltage supplied to units terminals is not below or
above listed range limits.
2. Maximum allowable voltage unbalance between phases is 2 %
3. MCA/MFA MCA = 1.25 * FLA
MFA ≤ 4 * FLA
(Next lower standard fuse rating. Min. 15 A)
4. Select wire size based on the MCA
5. Instead of fuse, use circuit.