MultiSITE CRC 1 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
CONFIGURATION SCREENS
ODU (0)
Silnt Mde Cntrl Loc
4/4 Installer / General
Prio Cool (2)
ODU Cyc Prio (56)
45 Min (0)
Therm Off Delay (56)
Parameter Parameter Settings Denition
Silnt Mde Cntrl Loc Choices: 0 = "ODU(0)" 1 = "Remote1(1)"
Default value = ODU(0)
Reduces the refrigerant noise during IDU initialization in
heating mode
ODU Cyc Prio Choices: “Disable” “Standby(1) “Prio
Cool(2)”
Default value = “Disable
When ODU Cyc Prio(56) is set to Standby(1) on the
CRC1, if the ODU is in cooling mode and the slave IDU
calls for heating, the slave IDU goes thermal o󰀨 and
stays in cooling mode.
When ODU Cyc Prio(56) is set to Priority Cool(2) on the
CRC1, if the ODU is in heating mode and the slave IDU
calls for cooling, the IDU will wait the amount of time set
by Therm O󰀨 Delay(56) after the master IDU is heating
thermal satised and the ODU will then switch to cooling
mode.
Therm O󰀨 Delay Choices: “45 min(0)” “30 min(1)”
“60 min(2)” “90 min(3)” “120 min(4)”
Default value = “45 min(0)
Time duration for IDU thermal o󰀨 delay.

Other manuals for LG MultiSITE CRC1 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MultiSITE CRC1 Series and is the answer not in the manual?

LG MultiSITE CRC1 Series Specifications

General IconGeneral
BrandLG
ModelMultiSITE CRC1 Series
CategoryRemote Control
LanguageEnglish

Related product manuals