Temperature Settings
Press the Temperature Settings button on the Installer screen to display the Temperature Settings screen. Press the right
arrow button to display the second page of the Temperature Settings screen.
1/2 Temperatu re S ettings
Parameter Parameter Settings Denition
Temp Sens Loc (4) 1 = “RC” (1)”, 2 = “IDU (2)”, 3 = “2TH (3)”
Default value = RC(1)
Selects between sensing temperature at the remote
controller RC(1), the indoor unit IDU(2), or both
sensors 2TH(3)
Setpoint °C Prec. (17) 1°C(0), 0.5°C(1)
Default value = 1°C(0)
Chooses whether to display Celsius temperatures
with 0.5 degree resolution or not
Single SP Deadband 1 = “2°F (1)” 5 = “10°F (5)”
2 = “4°F (2)” 6 = “12°F (6)”
3 = “6°F (3)” 7 = “14°F (7)”
4 = “8°F (4)”
Default value = Dual SP (when supported)
Dierential temperature between the heating
setpoint (the value chosen as your setpoint) and
cooling setpoint
Heat Therm(15) 0 = “Default (0)”
1 = “8°F/12°F (1)”
2 = “4°F/8°F (2)”
3 = “-2°F/2°F (3)”
4 = “-1°F/1°F (4)”
Default value = Default(0)
Provides an adjustable band around the heating
setpoint through selectable heating thermal on/o
values
Cool Therm(27) 0 = “1°F/-1°F (0)”
1 = “12°F/8°F (1)”
2 = “8°F/4°F (2)”
3 = “2°F/-2°F (3)”
Default value = 1°F/-1°F (0)
Provides an adjustable band around the cooling
setpoint through selectable cooling thermal on/o
values