EasyManuals Logo
Home>Manitowoc>Ice Maker>CVD2075

Manitowoc CVD2075 User Manual

Manitowoc CVD2075
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
–13–
ELECTRICAL REQUIREMENTS
QuietQube
®
Ice Machines and
CVD
®
Condensing Units
3 Phase Scroll Compressor Rotation
CVD2075 3 PHASE ONLY
A trained and qualified technician must verify
compressor rotation at equipment startup or
compressor warranty will be void. Incorrect rotation of
a scroll compressor can be identified by:
Noisy compressor operation
Elevated suction pressure
Low discharge pressure
Compressor trips on overload protector
To change compressor rotation, reverse (exchange
locations) any two incoming power supply leads.
Ice Machine Head Section
Voltage
Phase
Cycle
Max. Fuse/
Circuit
Breaker
Total
Amps
Q0600C
Q0800C
Q1000C
SU1000C
Q1400C
QDUAL
115/1/60
230/1/50
15 amp
15 amp
1.1
0.6
Important
The QuietQube
®
Ice Machine Head Section and
CVD
®
Condensing Unit are wired independently
from each other.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc CVD2075 and is the answer not in the manual?

Manitowoc CVD2075 Specifications

General IconGeneral
BrandManitowoc
ModelCVD2075
CategoryIce Maker
LanguageEnglish

Related product manuals