Part Number Preliminary 6/11 127
Single & Twin Evaporator QuietQube® Models
Energized Parts Chart
Ice Making
Sequence of
Operation
Water
Pump
Harvest
Valve (s)
Air Pumps
Water Inlet
Valve
Water
Dump
Valve
Liquid Line
Solenoid
Valve
Contactor
Refrigeration
Compressor &
Condenser Fan
Motor
Length of
Time
Start-Up - Initial or After
Auto Shut Off
1. Water Purge
On Off Off Off On Off Off 45 Seconds
2. Refrigeration
System Start-up
Pressure Equalization
Compressor Start
Off On On Off Off Off Off 5 Seconds
Off On On Off Off On On 5 Seconds
Freeze Sequence
3. Pre chill
Off Off Off
On
Cycles Off
then On/
Off, one
more time
Off On On
Initial Start-Up is 60
Seconds
30 Seconds
thereafter
4. Freeze
On Off Off Off On On
Until Ice contact
with ice thickness
probe