30 Part Number Preliminary 6/11
Location of ICVD Condensing Units
The location selected for the ICVD Condensing Unit
must meet the following criteria. If any of these criteria
are not met, select another location.
• ICVD0895/ICVD1095/ICVD1495/ICVD1895/
ICVD2195 Only - The air temperature must be at
least -20°F (-28.9°C) but must not exceed 130°F
(54.4°C).
• ICVD695/ICVD1195/ICVD2195/ICVD3095 Only -
The air temperature must be at least
-20°F (-28.9°C) but must not exceed 120°F
(48.9°C).
• The location must not allow exhaust fan heat and/
or grease to enter the condenser.
• The location must not obstruct airflow through or
around the condensing unit. See below for
clearance requirements.