114 Part Number 80-1505-3 6/11
HARVEST SEQUENCE
5. Water Purge
The air compressor (when used) and the harvest
valve(s) open at the beginning of the water purge to
divert hot refrigerant gas into the evaporator.
The water pump continues to run, and the water dump
valve energizes to purge the water in the water trough.
Single and twin evaporator models energize the water
fill valve for the last 15 seconds of the water purge
cycle.
CVD Condensing Unit:
When the refrigerant pressure is low enough to open
the fan cycling pressure control the condenser fan
motor stops.
* The IB0680C & S0680C ice machines do not use a
fan cycle control, therefore the condenser fan motor
will continue to run in the harvest cycle.
Energized Control Board Lights-
Single Evaporators = Left Bin (green), Harvest (red)
Twin Evaporators = Left & Right Bin (green), Harvest
(red)
Quad Evaporators = All Curtain Switches (green),
Liquid Solenoid (red), Dump Valve (red), Water Pump
(red), Harvest (red), All Harvest Valves (red)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc QuietQube SD1072C and is the answer not in the manual?

Manitowoc QuietQube SD1072C Specifications

General IconGeneral
BrandManitowoc
ModelQuietQube SD1072C
CategoryIce Maker
LanguageEnglish

Related product manuals