EasyManuals Logo
Home>Manitowoc>Ice Maker>QuietQube SD1072C

Manitowoc QuietQube SD1072C User Manual

Manitowoc QuietQube SD1072C
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
Part Number 80-1505-3 6/11 27
LOCATION OF CVD
®
CONDENSING UNIT
The location selected for the CVD Condensing Unit
must meet the following criteria. If any of these criteria
are not met, select another location.
CVD885/CVD1075/CVD1085/CVD1485/
CVD1885/CVD2085 Only - The air temperature
must be at least -20°F (-28.9°C) but must not
exceed 130°F (54.4°C).
CVD675/CVD685/CVD1185/CVD2075/CVD3085
Only - The air temperature must be at least
-20°F (-28.9°C) but must not exceed 120°F
(48.9°C).
CVD1486 Only- The air temperature must be at
least 50°F (10°C) but must not exceed 110°F
(43°C).
The location must not allow exhaust fan heat and/
or grease to enter the condenser.
The location must not obstruct airflow through or
around the condensing unit. See below for
clearance requirements.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc QuietQube SD1072C and is the answer not in the manual?

Manitowoc QuietQube SD1072C Specifications

General IconGeneral
BrandManitowoc
ModelQuietQube SD1072C
CategoryIce Maker
LanguageEnglish

Related product manuals