Part Number 000007661 11/16 101
RF2300/RFS2300 Troubleshooting
SELF-CONTAINED AIR-COOLED
Normal Operation
When the toggle switch is placed in the ON position the
following controls must be in the closed position before
the ice machine will start:
A. Bin Thermostat
B. High Pressure Cut-out Switch
C. Ice Chute Safety Switch
D. Low Pressure Switch
E. Low Water Level Switch
Placing the toggle switch in the ON position starts the
gear motor. After the rotation speed sensor verifies 10
minutes of correct rotation the time delay ends and
the compressor starts.The ice machine will continue to
make ice until ice contacts the bin thermostat. The ice
machine remains off until ice no longer contacts the bin
thermostat.
ROTATION SENSOR OPERATION
light Definition
Yellow Blinking Time Delay Period
Yellow Solid Normal Operation Sensing
Red Blinking Fault Time Delay Period
Red Solid Lockout - 8 Consecutive Faults
Remove/Restore Power To Reset