2524
Trouble Possible Cause Remedy
Hot water is not
the right
temperature
(too hot or too
cold).
Temperature set
point was reset due
to power outage.
Temperature set
point incorrect.
Flow is beyond
capacity.
Incoming water is
too warm.
Power outage restores default
settings and custom set points
must be re-entered to unit
A remote wired controller is
controlling temperature set
point. Release override control
of this remote (see “Remote
Control Panel Functions”) or
change set point to desired
temperature with that remote.
Desired water flow is above
maximum capacity of unit.
Reduce user flows to re-
establish control of temperature
If incoming water to unit is very
warm and the flow is just above
minimum requirements, the heat
generated by the burner while
operating at minimum capacity
can make the water hotter than
desired. Increase the hot water
user flow so that the burner
system can control the
temperature.
Hot water flow
produced is lower
than expected.
Water source is
restricted.
Heat exchanger in
unit is scaled.
Incoming water
temperature is
colder than
expected.
Check and fully open water inlet
valve(s)
Check and clean inlet water filter
Clean heat exchanger by flushing
per maintenance procedure.
Colder than normal incoming
supply water will reduce the
amount of hot water than can be
produced.
Trouble Possible Cause Remedy
Although the amount of heat
output from the unit is still at full
capacity, you must reduce the
user flow and operate within the
capacity range of the heater.
The hot water
coming appears
white and turbid.
S
appear when water
is heated. Air
dissolved in water
may evolve when
water is heated.
mall bubbles may
None. Normal operation.
Vent system
trouble.
Vent system is
restricted in some
manner.
Check air intake and exhaust
ducts to ensure they are not
damaged, corroded, blocked,
etc.
“Smoke” observed
coming from
exhaust system
during cold
temperatures.
Water vapor
produced during
combustion is
condensed in the
exhaust as the hot
gas is cooled by the
outside air.
None. Normal operation.
Water leaking from
safety valve outlet.
Water system is
operating above
design pressure.
Safety valve is
damaged.
Consult professional for system
review.
Replace safety valve. Consult
professional as required.
Blower fan noise
can be heard for
some time after
operation stops.
The blower is
designed to run for
30 seconds after
burner shuts off.
None. Normal operation.