Exhaust Fan
A variable speed exhaust fan controlled by a VFD is provided for all Economizer units with
either Constant Volume or VAV Supply Fans and on 100% Outside Air units with VAV Supply
Fans. Either a constant volume exhaust fan or a variable speed exhaust fan controlled by a
VFD may be provided on 100% Outside Air units with Constant Volume Discharge Fans.
The exhaust fan is turned on when one of the following sets of conditions is true:
All four of the following are true:
The Exhaust Fan is controlled by a VFD
The OA Dampers are at least open to the Minimum OA Position
The Minimum OA Position is greater than 0%
The building static pressure is above the building static pressure setpoint by more than the
deadband for longer than the Minimum Exhaust Fan Start Time (Default = 120 seconds)
OR
All four of the following are true:
The Exhaust Fan is controlled by a VFD
The OA Dampers are at least open to the Minimum OA Position
The Minimum OA Position is greater than 0%
The Exhaust Fan capacity is commanded to a value above the minimum value (Default =
5%) by a BAS for longer than the Minimum Exhaust Fan Start Time (Default = 120
seconds)
OR
The Exhaust Fan is Constant Volume AND
The Supply Fan has been commanded on for at least 4 seconds
The exhaust fan is turned off when one of the following sets of conditions is true:
All three of the following are True:
The Exhaust Fan is controlled by a VFD
The building static pressure is below the building static pressure setpoint by more than the
deadband
The Exhaust Fan capacity is at or below its minimum value (Default = 5%) for longer than
the Min Exhaust Fan Stop Time (Default = 120 seconds)
OR
Both of the following are True:
The Exhaust Fan is controlled by a VFD
The Exhaust Fan capacity is commanded to less than or equal to its minimum value (Default
= 5%) by the BAS for longer than the Minimum Exhaust Fan Stop Time (Default = 120
seconds)
OR
The Supply Fan is Off
Whenever a variable speed exhaust fan is on, its capacity will be modulated using a VFD. The
speed of the fan will be either (1) modulated to maintain the building static pressure at a
desired value or (2) set at a fixed speed provided by a Building Automation System via a
network.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MicroTech III RAH and is the answer not in the manual?

McQuay MicroTech III RAH Specifications

General IconGeneral
BrandMcQuay
ModelMicroTech III RAH
CategoryController
LanguageEnglish

Related product manuals