McQuay OM 920-1 85
Operators Guide
Examples of typical Min OA reset schedules.
If IAQ VDC is selected as the Min OA Reset, the Minimum OA Position is calculated based
on a 0-10V CO2 sensor input. The CO2 level is expressed as Parts per Million. The minimum
and maximum sensor input values (0-10V) and the corresponding minimum and maximum
PPM values are user editable. This calculated Minimum OA Position varies linearly from the
Demand Control Ventilation Limit at the value labeled “PPM @ DCV Limit” to the
Ventilation Limit at the value labeled “PPM @ VentLimit”. The “PPM @ DCV Limit” is not
allow to be set equal to or greater than the “PPM @ VentLimit”.
Example #1 Min OA reset type = IAQ VDC
This example assumes a CO2 sensor with a 0-2000PPM value over a range of 0-10VDC.
If the requirement is to have the OA damper be at its minimum (DCV Limit) when the CO2
levels are less than 800PPM and to be at its maximum (Vent Limit) when the CO2 levels are
greater than 1000PPM, the controller would be set up as follow:
Vent Limit = 100%
DCV Limit = 10%
Min OA reset type = IAQ VDC
Min V/mA = 0
Max V/mA = 10
PPM@DCV Limit = 800
PPM@Vent Limit = 1000
Min PPM = 0
Max PPM = 2000
In Figure 9 the Minimum OA Position would vary linearly from 10% outside air damper
position at 800PPM or less to 100% outside air damper position at 1000PPM or greater. This
would assume that the supply air fan speed remained at a constant 100%.
If EXT VDC is selected as the Min OA Rest, the Minimum OA Position is calculated based
on an external 0-10 VDC signal. If EXT mA is selected as the Min OA Reset, the Minimum
OA Position is calculated based on an external 0-20 mA signal. This calculated Minimum OA
Position varies linearly from zero % the editable minimum external signal to 100%at the
editable maximum external signal, but it is set no lower than the Demand Control Ventilation
Limit and no higher than the Ventilation Limit. If the editable minimum external signal is set
equal to the editable maximum external signal the external reset % reverts to the Ventilation
Limit.
Figure 9: Min OA Reset Type = IAQ VDC Example
Vent Limit =
(Default 20%)
Min Clg Speed =
(Default 40%)
40%
(Minimum)
100%
OA Damper Position %
Airflow – Min OA
Type = None
Damper Position vs. Fan Speed Chart
Lo Flow Vent Limit =
(Default 30%)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MicroTech III RAH and is the answer not in the manual?

McQuay MicroTech III RAH Specifications

General IconGeneral
BrandMcQuay
ModelMicroTech III RAH
CategoryController
LanguageEnglish

Related product manuals