16
When the mark is 0, start multi-step setting; When the flag is 1, a multi-step setting is performed. When
the multi-step setting is executing, write 0 to stop the multi-step setting. When you write 1 again, the
multi-step setting will be reexecuted from the first step.
1.5.5 Alarm function setting
The setting contents of the alarm function of the buffer of MTC-08-NT (BFM) are shown in table 1-12.
Table 1-12 MTC-08-NT buffer (BFM) alarm function Settings
Alarm dead zone
setting * 2
Default
value :10,denoted
by 0.1℃
Default
value :0,range:0~2
55
Range:0~999
* 1. #600 ~ #603: alarm enable, from which the user can determine the type of alarm required to enable.
#600 set the alarm type 1, #601 set the alarm type 2, and so on. MTC-08-NT offers 14 alarm types, four
of which can be selected simultaneously (see 5.3.1 alarm type). For different channels, the alarm values
of 1 ~ 4 alarm determined by #600 ~ #603 are set by #606 ~ #609, #610 ~ #613, #614 ~ #617, #618~
#621 、#622~#625、#626~#629、#630~#633、and #634~#637 respectively.
* 2. #604: set the dead zone for each channel's alarm mode. In order to avoid repeated occurrence of
alarm state and non-alarm state when the measured value fluctuates near the alarm setting value, an
alarm dead zone can be set. Setting range: 0 ~ 999; Default value: 10; Unit: 0.1℃/℉. See 5.3.2 alarm
dead zone.
* 3. #605: number of alarm delay. Set the range from 0 to 255. If the measured value in the alarm range is
still within the alarm range after the set number of delayed alarm, the alarm will be given. See 5.3.3 alarm
delay.