CCM-270A/WS
30 201807
CCM-270A/WS Service Manual
1.7 Pre Installation Settings
(IP Settings): The IP settings are required to be done in order that the computer that is being used to access the website of
CCM-270A/WS is able to find the CCM-270A/WS device. To make this happen, we are required to make sure that the
computer has its IP configured. In this section, we have discussed about this setting.
Local Network Connections
The CCM-270A/WS uses an Ethernet port/Wi-Fi to connect to the local area network. The IP addresses of the computer or
other similar equipment and that of CCM-270A/WS must be located in the same subnet segment. The IP of the computer
need to be changed into one that is in the same subnet as that of the CCM-270A/WS gateway. For doing the concerned
settings, the procedure is given as below.
IP Settings
The default IP of the CCM-270A/WS is 192.168.100.40:8000 with subnet mask of 255.255.255.0. For the IP of a computer
or other similar equipment, we need to manually configure the static IP that must be within 192.168.100 segment with
255.255.255.0 as the subnet mask. If the computer only connects to the CCM-270A/WS, then we would need multiple IP
addresses. The following figure shows the implementation method (Windows 7 system as an example).
1. Configure Single IP Address:
For the CCM-270A/WS gateway, to connect with the computer it needs to be verified that it is in the same IP segment as
the computer. To make this happen, we need to make sure that proper IP Configuration settings have been done. Following
are the steps that need to be followed to complete the IP settings:
Default IP of CCM-270A/WS is 192.168.100.40:8000; subnet mask is 255.255.255.0. The gateway's IP address and server
must be in the same subnet area. If you want to modify the gateway's IP address through the web page, you need to
manually configure static IP address of the PC and static IP must meet the following requirements: within 192.168.100
segment, subnet mask is 255.255.255.0. The user just needs to follow the following simple steps shown below in a step by
step dialog box manner for Windows7. The user just needs to follow these simple steps to configure the IP.
Dialog box1: Open the Network and Sharing Center of the computer for which the IP configuration are required to be
done.
Dialog Box 2: Select the LAN cable network through which the CCM-270A/WS is connected to the computer.
*Make sure not to connect the computer with any other wireless network while using CCM-270A/WS.
Dialog Box3: Open the Properties dialog box from the Network and Sharing Center tab.
Dialog Box4: Select the IPV4 settings.
Dialog Box5: Make sure that the configured IP of the computer is in the subnet 192.168.100. xx (where xx can be between
00 to 255 except for the value of the IP of CCM-270A/WS.