17.4.9 Over-voltage or under-voltage protection diagnosis and solution (P1)
Error Code
P1
Malfunction conditions
Abnormal increases or decreases in voltage are detected by
checking the specified voltage detection circuit.
Potential causes
Power supply issues
System leakage or blockage
Faulty PCB
Trouble shooting:
Check the power supply. Is it
in working order?
Check the connections and
w i r e s . Are they in working
order?
Turn off the unit
No
Yes
No
Ensure proper connections or
replace the wires
Yes
Replace the reactor
Yes
No Replace the IPM board
Turn power on and while the unit is on
standby, check if the voltage between P
and N is at DC 310V, 340V or 380V?
Then start up the unit and measure the
voltage between P and N. Is it in now
between 220V~400V?
Check the reactor. Is it in
working order?
Yes
No
Replace outdoor main PCB
Remark:
Measure the DC voltage
between P and N port.
The normal value should
be around 310V.340V or
380V

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MCA3U-09HRFN1-M(C) and is the answer not in the manual?

Midea MCA3U-09HRFN1-M(C) Specifications

General IconGeneral
BrandMidea
ModelMCA3U-09HRFN1-M(C)
CategoryAir Conditioner
LanguageEnglish

Related product manuals