V4+R VRF 50/60Hz
201608 65
Part 5 - Diagnosis and Troubleshooting
4.9 xH0, H1 Troubleshooting
Digital display output 4.9.1
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
Description 4.9.2
1H0 indicates a communication error between the main control chip and the compressor A inverter driver chip.
2H0 indicates a communication error between the main control chip and the compressor B inverter driver chip.
H1 indicates a communication error between the main control chip and the communication chip.
All units stop running.
Error code is only displayed on the unit with the error.
Possible causes 4.9.3
Power supply abnormal.
Transformer malfunction.
Interference from a source of electromagnetic radiation.
Main PCB damaged.