5 EARTHING
It is vital that all MX-ONE hardware building blocks are properly connected to a
common earth.
Make sure that the different units, the MX-ONE Service Node, the Standard Server, the
MX-ONE Lite, the MX-ONE Classic, the AC/DC unit and the fan unit, are connected to
the common earth when these units are screwed into a 19” rack.
Also make sure that MX-ONE equipment that is located outside of the racks, like, for
example, voice recording equipment, are properly connected to the common earth.
At both ends of the grounding conductor the units shall be free from paint or other insu-
lating material.
Note: The earth resistance shall not exceed 10 milli ohms.
For more details about Earthing, see installation instructions for INSTALLATION
PREPARATION AND EARTHING.