1.2.2 Range of usage & limitations
Model
302 series
Item
Limitations
Return air temp
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Power source voltage
Voltage at starting
Cycle Time
Stop Time
Dew point temperature: 28˚C or less, relative humidity: 80% or less
Indoor unit:18~30˚CD.B Outdoor unit:-15~43˚CD.B
Max. 50m
7 minutes or more (4 minutes or more from start to stop) or (3 minutes or more from stop to start)
3 minutes or more
Min. 85% of rating
Rating ± 10%
Compressor
stop/start
Frequency
Max. 30m (Outdoor unit is higher)
Max. 15m (Outdoor unit is lower)
Cooling
Heating Indoor unit:18~30˚CD.B Outdoor unit:-10~24˚CD.B