8 - 10
8. LOADING AND INSTALLATION
8.4.2 Installation
Installation location of the main base unit and the extension base unit is shown below.
Figure8.1 Parallel installation
Figure8.2 Series installation
Figure8.3 Distance between the front face of the
programmable controller and other devices
Figure8.4 Vertical installation
(not allowed)
Figure8.5 Horizontal installation
(not allowed)
Indicates the location of ceiling of
the panel, wiring duct or other part.
30mm (1.18inch)
or more
Main base Extension base
30mm (1.18inch)
or more
This shows the position of the
panel's ceiling, wiring duct, or
components.
30mm (1.18inch) or more
Main base
Extension base unit
(A5 B(S1), A1S B(S1))
80mm
(3.15inch) or more
Duct (Height of
50mm (1.97inch)
30mm (1.18inch) or more
30mm (1.18inch) or more
30mm (1.18inch) or more
30mm
(1.18inch) or more
80mm
(3.15inch) or more
Duct (Height of
50mm (1.97inch)
or less)
Main base
30mm
(1.18inch) or more
Extension base unit
(A1S5 B(S1),
A1S6 B(S1))
Panel, etc.
Programmable
controller
Contactor
relay, etc.
100mm (3.94 inch) or more
Door

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-A A2USHCPU-S1 and is the answer not in the manual?

Mitsubishi MELSEC-A A2USHCPU-S1 Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-A A2USHCPU-S1
CategoryController
LanguageEnglish

Related product manuals