172
-
(10) Outline of automatic operation
(a) Determination of operation mode
The unit checks the room temperature and the outdoor air temperature after operating the indoor and outdoor blowers for 20
seconds, determines the operation mode and the room temperature setting correction value, and then begins in the automatic
operation.
(b) Within 30 minutes after either auto or manual operation stops, if auto operation is started, or if you switch to auto operation during
manual operation, the system runs in the previous operation mode.
(c) The temperature is checked 1 time in 30 minutes after the start of operation, and if the judgment differs from the previous operation
mode, the operation mode changes.
(d) Setting temperature can be adjusted within the following range. There is the relationship as shown below between the signals of the
wireless remote control and the setting temperature.
Signals of wireless remote control (Display)
–6 –5 –4 –3 –2 –1 ±0+1+2+3+4+5+6
Setting
Cooling 18 19 20 21 22 23 24 25 26 27 28 29 30
temperature
Dehumidifying 18 19 20 21 22 23 24 25 26 27 28 29 30
(11) Outline of fan operation
(a) Operation of major functional components
(b) HIGH POWER operation (“HI POWER” button on the remote control : ON)
The following operation is performed for 15 minutes without relation to the set temperature or fan speed setting.
52C
Indoor fan motor
Outdoor fan motor
Flap and louver
Speed 9 Speed 8 Speed 8
OFF
OFF
Depend on the flap and louver control
Speed 6 Speed 4 Speed 2
High power AUTO HIGH MED LOW ECONO
Functional
components
Fan speed switching
Indoor unit fan
Outdoor unit fan
Compressor
Speed 9 fixed
OFF
OFF
Note (1) Protective functions will actuate with priority even during the HIGH POWER operation.
27.5
25.5
19.5
18
30
Room temperature (
˚C)
Cooling
Dehumidifying
Outdoor temperature (˚C)