00-02-0796 - 39 - 08-26-11
DATA ERROR is displayed in place of a parameter
value
The ECU is sending a message that there is a data error
with this parameter. Alternatively, (PV101 only) FUEL
LEVEL has been selected for display, ANALOG INPUT has
been set to FUEL LEVEL, but no Murphy Fuel Sender has
been connected to the analog input.
One of the 4-UP quadrants is empty
No parameter has been selected for display in this
quadrant.
Display is not readable, either very dim or very dark
The LCD contrast may have been over or under adjusted.
Press and hold the MENU key for approximately 5 seconds.
This will reset the LCD contrast setting to factory default.
PVA Gages not working
When PVA Gages are connected and do not seem to work, go
to the Utilities menu and select Remove all Gages.