NHB Service Manual 105
Version 1.0
5.2.11 110Error
Error occurrence conditions and check items
Error Description
E110
Air pressure error
The system senses the air volume and the RPM signal, and displays 110E on the front panel in
the following cases:
1. When the initial fan auto-adjust is not performed.
2. When the unit capacity reaches up to 95% of the maximum heat during combustion, and
APS is not up the standard value.
Check items
1. Check if the venturi (burner) hole is clogged.
2. Check if the condensation drain line or the drain is clogged.
3. Check the flue and exhaust to verify proper installation and clearances. (Circulation of
exhaust gas generates noise.)
4. Check if the air supply/exhaust flue is clogged (rainwater may collect inside from an
improperly installed air supply/exhaust pipe).
5. Defective air pressure sensor or PCB.
6. Make sure that venting is sloped downwards towards the unit for proper condensate
drainage.
7. Make sure that internal damper is moving freely with no obstructions.
Is there any restriction in
airflow?
Remove all the restrictions in
airflow around unit and check the
vent pipe for obstructions.
Reset or Restart
No
Yes

Table of Contents

Other manuals for Navien NHB-150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Navien NHB-150 and is the answer not in the manual?

Navien NHB-150 Specifications

General IconGeneral
ModelNHB-150
CategoryBoiler
Maximum Input150, 000 BTU/h
AFUE95%
Vent TypeDirect Vent
Fuel TypeNatural Gas or Propane
Min. Input (NG)15, 000 BTU/h
Min. Input (LP)15, 000 BTU/h
Voltage120 V
Water Connection Size1 inch NPT
Gas Connection Size3/4 inch NPT
Vent Diameter3"

Related product manuals