NHB Service Manual 107
Version 1.0
5.2.12 205Error
Error conditions and Check Items
Error Description
E205
Heat exchanger output temperature
sensor open
If an error (open: 14°F (-10°C) or lower) in the heat exchanger input temperature sensor is
detected, the system displays the 205E error on the front panel. If this occurs, the boiler initiates
shutdown.
Check items
1. Check if the heat exchanger output temperature sensor connector is wet due to any
reason, including leakage.
2. Replace the defected heat exchanger output temperature sensor.
3. Check circulation pump (external type) operating status and for proper flow through the
space heating line.
4. Check the voltage on the PCB to verify proper power to the pump. If there is no voltage,
bleed out air from the system before resetting the unit. If issue persists, replace the pump.
Is the outlet thermistor
normal?
Check connector
(#7 and #8 of CN 13)
Replace outlet thermistor
Resistance between #7 and #8 of CN13
is from 0.437kΩ to 176kΩ at normal
condition. (see page 63-64 for Wiring
Diagram)
No
Yes
Before measuring resistance of the
thermistor, detach the connector
from the PCB.

Table of Contents

Other manuals for Navien NHB-150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Navien NHB-150 and is the answer not in the manual?

Navien NHB-150 Specifications

General IconGeneral
ModelNHB-150
CategoryBoiler
Maximum Input150, 000 BTU/h
AFUE95%
Vent TypeDirect Vent
Fuel TypeNatural Gas or Propane
Min. Input (NG)15, 000 BTU/h
Min. Input (LP)15, 000 BTU/h
Voltage120 V
Water Connection Size1 inch NPT
Gas Connection Size3/4 inch NPT
Vent Diameter3"

Related product manuals