Electrical data
3X230 V
F1145-15
230V 3N ~ 50HzRated voltage
82.5A
rms
Starting current
11(16)A
rms
Max operating current including 0 kW immersion heater (Recommended fuse rating).
28(32)A
rms
Max operating current including 2 kW immersion heater (Recommended fuse rating).
35(40)A
rms
Max operating current including 4 kW immersion heater (Recommended fuse rating).
35(40)A
rms
Max operating current including 6 kW immersion heater (Recommended fuse rating).
46(50)A
rms
Max operating current including 9 kW immersion heater, requires reconnection (Recommended fuse rating).
2/4/6/9kWAdditional power
35 – 185WOutput, Brine pump
10 – 87WOutput, Heating medium pump
IPX1BEnclosure class
Equipment Compliant with IEC 61000-3-12
For Connection Design Purposes, Compliant with IEC 61000-3-3 technical requirements
F1145-17
230V 3N ~ 50HzRated voltage
84.5A
rms
Starting current
13(16)A
rms
Max operating current including 0 kW immersion heater (Recommended fuse rating).
31(32)A
rms
Max operating current including 2 kW immersion heater (Recommended fuse rating).
38(40)A
rms
Max operating current including 4 kW immersion heater (Recommended fuse rating).
38(40)A
rms
Max operating current including 6 kW immersion heater (Recommended fuse rating).
49(50)A
rms
Max operating current including 9 kW immersion heater, requires reconnection (Recommended fuse rating).
2/4/6/9kWAdditional power
35 – 185WOutput, Brine pump
10 – 87WOutput, Heating medium pump
IPX1BEnclosure class
Equipment Compliant with IEC 61000-3-12
For Connection Design Purposes, Compliant with IEC 61000-3-3 technical requirements
NIBE F1145Chapter 12 | Technical data72