Adjustment, charge
flow
For correct function of the heat pump over the entire
year, the charge flow must be correctly adjusted.
If an NIBE indoor module VVM or accessory controlled
charge pump is used for the control module SMO, the
control tries to maintain an optimal flow across the heat
pump.
Adjustment may be required, especially for charging a
separate water heater. It is therefore recommended to
have the option of adjusting the flow across the water
heater using a trim valve.
1.
Recommendation if there is insufficient hot water
and information message "high condenser out" dur-
ing hot water charging: increase the flow
2.
Recommendation if there is insufficient hot water
and information message "high condenser in" during
hot water charging: reduce the flow
35Chapter 6 | Commissioning and adjustingNIBE F2120

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe F2120 Series and is the answer not in the manual?

Nibe F2120 Series Specifications

General IconGeneral
TypeAir/Water Heat Pump
Operating Temperature Range-25°C to +45°C
RefrigerantR410A
Max. Flow Temperature65°C
Heating Capacity8-20 kW
Power Supply3-phase, 400V
SCOP5.0 (Model dependent, refers to average climate, low temperature application)