Page #46 background imageLoading...
Page #46 background image
Technical specifications
IP 24
128F2120 1x230V
Heating
Output data according to EN 14511, partial load
1)
7.35 / 2.43 / 3.025.17 / 1.72 / 3.00kW/kW/--7/35 Capacity / Power input / COP
EN 14511
5.21/ 1.22 / 4.274.03 / 0.91 / 4.43kW/kW/-2/35 Capacity / Power input / COP
EN 14511
5.27 / 1.49 / 3.544.07 / 1.16 / 3.51kW/kW/-2/45 Capacity / Power input / COP
EN 14511
3.54 / 0.69 / 5.123.57 / 0.78 / 4.57kW/kW/-7/35 Capacity / Power input / COP
EN 14511
3.64 / 0.91 / 4.003.66 / 0.98 / 3.74kW/kW/-7/45 Capacity / Power input / COP
EN 14511
MaxMaxOutd. temp: / Supply
temp.
Cooling
4.69 / 1.70 / 2.763.80 / 1.28 / 2.9735 / 7 °C
Output data according to EN 14511
Δ
T5K
Capacity/power input/EER
5.44 / 1.73 / 3.155.10 / 1.37 / 3.7335 / 18 °C
Electrical data
230V ~ 50HzRated voltage
1614A
rms
Max operating current, heat pump
1513A
rms
Max operating current, compressor
4540WMax output, fan
1616A
rms
Fuse
IP24Enclosure class
Refrigerant circuit
R410AType of refrigerant
2,088GWP refrigerant
ScrollType of compressor
2.62.4kgVolume
5.435.01tCO
2
-equivalent (The cooling circuit is hermetically sealed.)
4.5MPaCut-out value pressure switch HP (BP1)
0.7MPaDifference pressostat HP
0.12MPaCut-out value pressostat LP
0.7MPaDifference pressostat LP
Brine
3,4002,400m
3
/hMax airflow
-25 / 43°CMin/Max air temp, max
reverse cycleDefrosting system
Heating medium
0.45 (4.5 bar)MPaMax system pressure heating medium
0.11 / 0.440.08 / 0.32l/sMin/Max flow
26 / 65°CMin/Max HM temp continuous operation
G1 1/4" external threadConnection heating medium F2120
G1 external threadConnection heating medium flex pipe
Dimensions and weight
1,2801,130mmWidth
612610mmDepth
1,1651,070mmHeight with stand
160150kgWeight (excl. packaging)
Miscellaneous
064 136064 134Part No.
NIBE F2120Chapter 11 | Technical data46

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe F2120 Series and is the answer not in the manual?

Nibe F2120 Series Specifications

General IconGeneral
TypeAir/Water Heat Pump
Operating Temperature Range-25°C to +45°C
RefrigerantR410A
Max. Flow Temperature65°C
Heating Capacity8-20 kW
Power Supply3-phase, 400V
SCOP5.0 (Model dependent, refers to average climate, low temperature application)