14 – ENGLISH
7. the courtesy light will start ashing once every second (1
Hz) to signal the need to run the MANDATORY “Automatic
Force Search” procedure. During the “Automatic Force
Search” procedure, check that there are no assembly and
adjustment defects, or other anomalies, for example points
of excessive friction
8. impart a movement command (for example: through the
“SbS”, “OPEN” inputs) to start the” Automatic Force
Search” procedure: 3 complete cycles will be performed.
If the above-mentioned procedure is interrupted, it can be
restarted by selecting the “SbS”, “Open”, “Close” com-
mands.
During these manoeuvres, the control unit memorises the force
required for the opening and closing movements.
FUSE
LED
FUSE
L7
L1
L2
L4
L5
18
The position learning procedure can be redone at any time, even
after installation; simply repeat it from the beginning. If only a single
position must be modied, repeat the reduced procedure only.
m
It is important that the “Automatic Force Search”
procedure is not interrupted, e.g. by a STOP com-
mand. If the “positions”, “motor opening speed”,
“motor closing speed” and “motor rotation di-
rection” parameters are modied, the “Automat-
ic Force Search” procedure will be automatical-
ly re-proposed by the control unit. The procedure
must terminate correctly and autonomously, that is,
without any interruptions: the procedure will remain
pending even after a blackout.
5.4 CHECKING THE DOOR MOVEMENT
Once the leaf length has been learned, it is advisable to carry out
a few manoeuvres in order to verify that the door moves properly.
FUSE
LED
FUSE
19
To do this:
1. press the
p
button to command an “Open” manoeuvre;
check that the door opens properly without any speed varia-
tions; only when the leaf reaches the “RA1” position, it must
reach the minimum speed and stop at the “A1” maximum
opening position
2. press the
q
button to command a “Close” manoeuvre;
check that the door closes properly without any speed varia-
tions; only when the leaf reaches the “RA0” position, it must
reach the minimum speed and stop at the “A0” maximum
closing position
3. during the manoeuvre, check that the warning light ashes
at intervals of 0.5 seconds on and 0.5 seconds off
4. open and close the gate several times to make sure that
there are no points of excessive friction and that there are no
defects in the assembly or adjustments
5. check that the gearmotor is fastened in a solid, stable and
suitably resistant manner even during sudden door acceler-
ation or slowdown movements.
5.5 CONNECTING OTHER DEVICES
If the user needs to power external devices, such as a proximity
reader for transponder cards or the light of the key selector switch,
power can be tapped as shown in the gure.
The power supply voltage is 24Vc -30% ÷ +50% with a maximum
available current of 100mA.
STOP
SBS
(-)(+)
20
TESTING AND COMMISSIONING
6
6 TESTING AND COMMISSIONING
These are the most important phases of the automation’s con-
struction, as they ensure maximum safety of the system. The test
can also be used to periodically verify the devices making up the
automation.
m
Testing and commissioning of the automation must
be performed by skilled and qualied personnel,
who are responsible for the tests required to ver-
ify the solutions adopted according to the risks
present, and for ensuring that all legal provisions,
standards and regulations are met, in particular all
the requirements of the EN 12445 standard, which
denes the test methods for checking door auto-
mations.
The additional devices must undergo specic testing, both in terms
of their functions and their proper interaction with the control unit.
Refer to the instruction manuals of the individual devices.