AFP-300/AFP-400
PN 15842:K 7/23/2002 55
N.5 System and Point Annunciation
The control panel's annunciation points are divided into nine ACS Selection
Groups of 64 points. Table N-1, which follows, summarizes the ACS Selection
Groups and what an annunciator displays if a group is selected. The
AFP-300/AFP-400 installation manual provides a complete listing of the points
within the ACS Selection Groups and instructions on programming the panel for
addressable annunciators.
Note: Annunciators configured for point annunciation:
• Do not respond to any status change that is not within its ACS Selection
Group. This includes system alarm or system trouble.
• Do mask status changes for point number 1 of the start address selection.
• Do not respond to System Reset, Acknowledge, or Alarm Silence.
• Do not use the battery saving feature (100 mA battery load)
ACS
Selection
Group Annunciator Display
1 Control Panel Status and Zones 1-56
2 Zones 57-99, NAC Ckts 1-4 and 16 Special Zones
3 Intelligent Modules 101 to 164
4 Intelligent Modules 201-264 (AFP-400 only)
5 Intelligent Modules 165-196 and 265-296 (AFP-400 only)
6 Detectors 101 to 164 on SLC loop 1
7 Detectors 201-264 on SLC loop 2 (AFP-400 only)
8 Detectors 165-196 and 265-296 (AFP-400 only)
9 Panel Output Circuit Modules (64 points)
A Programmable annunciator group A; requires VeriFire™ 400
software to program
B Programmable annunciator group B; requires VeriFire™ 400
software to program
* or 0 Annunciator Not Installed At Address
Table N-1 Zone and Point Mapping With AFP-300/AFP-400